Inspection History Details
Inspection Status: Approved
Inspection History: INSP - AST/UST
Case Number - T07FR00973
Inspection Description - INSP - AST/UST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2007 | INSP - AST/UST | Approved | Final inpection passed. Tested all dispenser with the emergency shutoff. No leaks found. Tested the shunt trip breaker. | |