Case: T07FR00973

Parcel: 11615085A

Inspection Status: Approved

Inspection History: INSP - AST/UST

Case Number - T07FR00973

Inspection Description - INSP - AST/UST

Inspection Status - Approved

Date Description Inspector Results Comments
06/27/2007 INSP - AST/UST Approved Final inpection passed. Tested all dispenser with the emergency shutoff. No leaks found. Tested the shunt trip breaker.
06/12/2007 INSP - AST/UST Continued Primary piping passed pressure and soap test. Sumps and overfill protection passed water test.
05/18/2007 INSP - AST/UST Continued Excavation inspected, set 2 USTs (10K,15K) and deadmen. Both tanks arrived under vacuum at 0.7 bar. Tanks were sloped at 1/4" per foot and stabilized with pea gravel. I will check gages on monday after backfilled to 12" from top of tank.