Inspection Status: Approved
Inspection History: INSP - AST/UST
| Date |
Description |
Inspector |
Results |
Comments |
| 06/27/2007 |
INSP - AST/UST |
|
Approved |
Final inpection passed. Tested all dispenser with the emergency shutoff. No leaks found. Tested the shunt trip breaker. |
| 06/12/2007 |
INSP - AST/UST |
|
Continued |
Primary piping passed pressure and soap test. Sumps and overfill protection passed water test. |
| 05/18/2007 |
INSP - AST/UST |
|
Continued |
Excavation inspected, set 2 USTs (10K,15K) and deadmen. Both tanks arrived under vacuum at 0.7 bar. Tanks were sloped at 1/4" per foot and stabilized with pea gravel. I will check gages on monday after backfilled to 12" from top of tank. |