Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1.FIRE NOT NOTED PROPERLY DUE TO LACK OF MANINTANCE TO SIGNALING DEVICE. LOW BATTERY THE CAUSE. 2. ALL SYSTEM TO ALL BUILDING MUST BE TESTED AND REPAIRED. 3. DOCUMANTION MUST BE SUBMITTED TO TFD OF THE MAINTANCE AND REPAIRS. 4. SYSTEM MUST BE SERVICED ANNUNALY |
|
| 05/11/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ALARM SYSTEM REPAIRED FOR BUILDING # 3 |