Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
| 05/11/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.4.1 - Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed. _____ replace power tap with approved power strip, break room TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace orange extension cord under wall shelving unit with approved power strip or permanent wiring. Power strips shall be plugged directly into receptacle. |