Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Continued
Inspection History: VIOL - COMPRESSED GASES
Case Number - T07FR00926
Inspection Description - VIOL - COMPRESSED GASES
Inspection Status - Continued
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/19/2007 | VIOL - COMPRESSED GASES | Continued | Oxygen bottles secured, seperated by distance of 36" from other combustables but not in a seperate area. Code may require seperation by fire resistive wall. | |
05/10/2007 | VIOL - COMPRESSED GASES | Correction Required | TFC 3003.3 - Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. _____ Secure gas cylinders to avoid accidental dislodgment, in an approved manner. 3006.2 Medical gases shall be stored in areas dedicated to the storage of such gases without other storage or uses. _____ Provide isolated storage for medical gasses. |