Case: T07FR00913

Parcel: 117033520


Addresses:

638 E UNIVERSITY BL


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00913

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
05/25/2007 VIOL - MEANS OF EGRESS Approved All violations abated 5/25.
05/10/2007 VIOL - MEANS OF EGRESS Correction Required Thumblatch lock used in conjunction with panic hardware, Third floor exit to balcony.____

1027.6 Panic hardware. When panic and fire exit hardware is installed, whether required or not, panic or exit fire hardware shall be the only locking device on the door except where otherwise permitted in this code.
***Remove thumblatch lock.
05/10/2007 VIOL - MEANS OF EGRESS Correction Required Non-functional doorknob installed on rear exit door.____

1027.2 Reliability. Required exit accesses, exits or exit discharges
shall be continuously maintained free from obstructions
or impediments to full instant use in the case of fire or other
emergency. Security devices affecting means of egress shall be
subject to approval of the fire code official.
***Remove doorknob.