Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | All violations abated 5/25. | |
| 05/04/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | All bedrooms need smoke detector coverage. 907.2.10.1.2 Groups R-2, R-3, R-4 and I-1. Single- or multiple- station smoke alarms shall be installed and maintained in Groups R-2, R-3, R-4 and I-1 regardless of occupant load at all of the following locations: 1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. 2. In each room used for sleeping purposes. 3. In each story within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics. ****Install smoke detectors in all sleeping quarters, including house mothers' bedroom.____ |
|
| 05/04/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | A smoke detector Maintenance record log shall be submitted to TFD. 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed ****Test detectors, submit record.____ |