Case: T07FR00881

Parcel: 132191230


Addresses:

2001 E IRVINGTON RD


Inspection Status: Violation

Inspection History: INSP - REINSPECTION

Case Number - T07FR00881

Inspection Description - INSP - REINSPECTION

Inspection Status - Violation

Date Description Inspector Results Comments
06/11/2007 INSP - REINSPECTION Violation On 5-03-07, a fire prevention inspection was conducted at 2001 E. Irvington, Tucson Arizona.

On 5-22-07, a re-inspection was conducted and the following International Fire Code 2003 Violation(s) was noted:

Enclosed is a copy of your Certificate of Occupancy.

Boxes are stored on top of cooler without fire protection. This is in violation of 903.1.1.

903.3.1.1NFPA13 sprinkler systems. Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler
system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13 except as provided in Section 903.3.1.1.1.


The Tucson Fire code gives you the choice of exempt locations.



903.3.1.1.1 Exempt locations. Automatic sprinklers
shall not be required in the following rooms or areas where such rooms or areas are protected with an approved
automatic fire detection system in accordance
with Section 907.2 that will respond to visible or invisible
particles of combustion. Sprinklers shall not
be omitted from any room merely because it is damp,
of fire-resistance rated construction or contains electrical
equipment.
1. Any room where the application of water, or
flame andwater, constitutes a serious life or fire
hazard.
2. Any room or space where sprinklers are considered
undesirable because of the nature of the
contents, when approved by the fire code official.
3. Generator and transformer rooms separated
from the remainder of the building by walls and
floor/ceiling or roof/ceiling assemblies having
a fire-resistance rating of not less than 2 hours.
4. In rooms or areas that are of noncombustible
construction with wholly noncombustible contents.

Boxes stored on cooler shall be removed or area shall be installed with fire sprinkler system.