Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2007 | VIOL - MEANS OF EGRESS | Approved | All violations have been corrected. | |
| 05/04/2007 | VIOL - MEANS OF EGRESS | Violation | IFC 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from impediments to full instant use. Replace damaged exit door on NW exit of factory floor. | |
| 05/04/2007 | VIOL - MEANS OF EGRESS | Violation | IFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Cause all of your emergency lighting to operate properly and replace batteries/bulbs where needed. ( NW exit of factory, fallen lights in stock area ) | |
| 05/04/2007 | VIOL - MEANS OF EGRESS | Violation | IFC1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. Remove slide bolt lock from exit door on SE corner of building near sprinkler riser. |
|
| 05/03/2007 | VIOL - MEANS OF EGRESS | Violation | IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Place illuminated exit signs at all required exits. | |
| 05/03/2007 | VIOL - MEANS OF EGRESS | Violation | IFC 1011.2 Illumination. Exit signs shall be internally or externally illuminated. Cause all of your exit signs to be illuminated. ( stock area, S exit, E exit near lunch room) |