Case: T07FR00833

Parcel: 117050150


Addresses:

424 N 4TH AV


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR00833

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
06/12/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 2003 IFC 906.7 906.6
NEED TO SERVICE AND TAG 2 EXTINGUISHERS IN THE DJ BOOTH AREA.
NEED TO MOUNT SAID EXTINGUISHER IN DJ BOOTH AREA.

K BOTTLE NEEDS TO BE MOUNTED IN ACCESSIBLE AREA IN KITCHEN.
DRY CHEM EXTINGUISHER IN KITCHEN NEEDS TO BE SERVICED AND TAGGED AND MOUNTED.
06/12/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 2003 IFC 904.4 SERVICE OF HOOD SYSTEM
NEED TO SE SERVICE TAG FOR HOOD SYSTEM. IF NOT, HAE SYSTEM SERVICED AND TAGGED.