Case: T07FR00817

Parcel: 132170010


Addresses:

4619 S PARK AV

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
07/18/2007 VIOL - MEANS OF EGRESS Approved All violations abated 7/18.
04/26/2007 VIOL - MEANS OF EGRESS Violation Doors (2) outfitted with slide bolts, double keyed locks.(Rear kitchen).___
1008.1.8.4 Bolt locks. Manually operated flush bolts or surface
bolts are not permitted.
1008.1.8 Door operations. Except as specifically permitted by
this section egress doors shall be readily openable from the
egress side without the use of a key or special knowledge or effort.
****Remove slide blots, Replace double keyed locks with an approved lock, such as a thumblatch.
04/26/2007 VIOL - MEANS OF EGRESS Violation Exit signs (2) need to be lit. (rear kitchen area)
1011.5.3 Power source. Exit signs shall be illuminated at all
times. To ensure continued illumination for a duration of not less
than 90 minutes in case of primary power loss, the sign illumination
means shall be connected to an emergency power system
provided from storage batteries, unit equipment or an on-site
generator.2003 IFC
Replace exit signs with approved, illuminated signs.