Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2007 | VIOL - MEANS OF EGRESS | Approved | All violations abated 7/18. | |
| 04/26/2007 | VIOL - MEANS OF EGRESS | Violation | Doors (2) outfitted with slide bolts, double keyed locks.(Rear kitchen).___ 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ****Remove slide blots, Replace double keyed locks with an approved lock, such as a thumblatch. |
|
| 04/26/2007 | VIOL - MEANS OF EGRESS | Violation | Exit signs (2) need to be lit. (rear kitchen area) 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator.2003 IFC Replace exit signs with approved, illuminated signs. |