Case: T07FR00817

Parcel: 132170010


Addresses:

4619 S PARK AV

Inspection Status: Approved

Inspection History: VIOL - FIRE RESIST.RATED CONST

Date Description Inspector Results Comments
07/18/2007 VIOL - FIRE RESIST.RATED CONST Approved All violations abated 7/18.
04/26/2007 VIOL - FIRE RESIST.RATED CONST Violation Hole in drywall. (Dish washing room).___
703.1 Maintenance. The required fire-resistance rating of
fire-resistance-rated construction (including walls, fire stops,
shaft enclosures, partitions and floors) shall be maintained.
Such elements shall be properly repaired, restored or replaced
when damaged, altered, breached or penetrated. Openings
made therein for the passage of pipes, electrical conduit, wires,
ducts, air transfer openings, and holes made for any reason shall
be protected with approved methods capable of resisting the
passage of smoke and fire. 2003 IFC
****Repair wall.