Case: T07FR00810

Parcel: 110113730

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR00810

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
05/25/2007 VIOL - FIRE PROTECTION SYSTEMS Approved
04/26/2007 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not mounted:
TFC 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm).

______Mount extinguishers in an approved manner.
04/26/2007 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not tagged / inspected:
TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

______ Extinguishers shall be maintained, inspected and tagged in accordance with this code.



Re-inspection date scheduled on or after May 10, 2007.
If you have any questions or concerns please call Inspector Cobb at 791-4502
Thank you,

_____________________________________________
Brian Cobb, Inspector, Tucson Fire Department