Inspection Status: Compliance
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR00787
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Compliance
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2007 | VIOL - FIRE PROTECTION SYSTEMS | Compliance | all violations corrected. | |
| 04/24/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | IFC 904.5.1 Wet chemical extinguishing systems for commercial cooking devices shall be inspected and tested every 6 monthes. Provide paperwork for current inspection/testing by a certified person / company. | |
| 04/24/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | IFC 906.2 Portable fire extinguishers shall be maintained in accordance with NFPA 10 and tested annually. Have 2 extinguishers tested and the empty extinguisher filled. | |
| 04/24/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | IFC 906.7 Hand held portable fire extinguishers shall be installed on the hangers or brackets supplied. Mount both extinguishers on the brackets in the kitchen. |