Case: T07FR00787

Parcel: 138241600


Addresses:

1681 W VALENCIA RD


Inspection Status: Compliance

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00787

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Compliance

Date Description Inspector Results Comments
05/10/2007 VIOL - BUILDING SVCS & SYSTEMS Compliance all violations corrected.
04/24/2007 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 605.5 Estension cords shall not be used as a substitute for permanent wiring. Remove the extension cord that is through the ceiling tile in the drive thru area.
04/24/2007 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 605.3 A working space of not less than 30 inches wide, 36 inches in depth, and 78 inches in height shall be provided in front of electrical panels. Remove the obstacles blocking the panel in the kitchen.
04/24/2007 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 605.6 Approved covers shall be provided for all switches. Adjust switch cover to main breaker in kitchen elevtrical panel, so switch parts are not exposed.