Inspection Status: Compliance
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 05/10/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Compliance |
all violations corrected. |
| 04/24/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
IFC 605.5 Estension cords shall not be used as a substitute for permanent wiring. Remove the extension cord that is through the ceiling tile in the drive thru area. |
| 04/24/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
IFC 605.3 A working space of not less than 30 inches wide, 36 inches in depth, and 78 inches in height shall be provided in front of electrical panels. Remove the obstacles blocking the panel in the kitchen. |
| 04/24/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
IFC 605.6 Approved covers shall be provided for all switches. Adjust switch cover to main breaker in kitchen elevtrical panel, so switch parts are not exposed. |