Case: T07FR00760

Parcel: 136210120


Addresses:

7777 E STELLA RD


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00760

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
03/23/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required In room 17 (door 154), there are numerous extension cords being used as a replacement for permanent electrical supply wiring. Remove these extension cords fromuse or replace them with permanent electrical wiring that is properly installed.
03/23/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required In room 17 (door 154) there are several flexible electrical power cords that are damaged and then spliced or taped. Remove these electrical cords from use or replace / repair them properly.
03/23/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required In room 17 (door 154) several temporary extension cords are being used by being run through opening or holes in ceilings and or walls. Remove these cords from use and replace with properly installed permanent wiring.