Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FLAMMABLE LIQUIDS
Case Number - T07FR00749
Inspection Description - VIOL - FLAMMABLE LIQUIDS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/19/2007 | VIOL - FLAMMABLE LIQUIDS | Approved | The last vent is in place. permit issued | |
07/12/2007 | VIOL - FLAMMABLE LIQUIDS | Continued | RI- Vent not yet installed | |
07/10/2007 | VIOL - FLAMMABLE LIQUIDS | Continued | Spoke with the roperty rep. They will install the last vent required. all other tank violations have been corrected. | |
06/18/2007 | VIOL - FLAMMABLE LIQUIDS | Continued | Precitation sent to Property owner Larson Baker. Compliance must be by July 02-07 | |
06/07/2007 | VIOL - FLAMMABLE LIQUIDS | Continued | The waste oil tank is now vented to the outdoors. Smaller tanks still need to be removed and larger permenant ones need emergency venting. | |
05/07/2007 | VIOL - FLAMMABLE LIQUIDS | Continued | SI- vent piping being installed. Good progress being made. | |
04/25/2007 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3404.2.7.3.3 Vent pipe outlets. Vent pipe outlets for tanks storing Class I, II or IIIA liquids shall be located such that the vapors are released at a safe point outside of buildings and not less than 12 feet (3658 mm) above the adjacent ground level. Vapors shall be discharged upward or horizontally away from adjacent walls to assist in vapor dispersion. Vent outlets shall be located such that flammable vapors will not be trapped by eaves or other obstructions and shall be at least 5 feet (1524 mm) from building openings or lot lines of properties that can be built upon. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent. 3404.2.7.3.4 Installation of vent piping. Vent piping shall be designed, sized, constructed and installed in accordance with Section 3403.6. Vent pipes shall be installed such that they will drain toward the tank without sags or traps in which liquid can collect. Vent pipes shall be installed in such a manner so as not to be subject to physical damage or vibration. · The normal vents for the new oil tanks shall be equipped with the normally closed vents or vented to the outside in accordance with these codes. · The normal vents for the waste oil tank must be vented to the outdoors in accordance with these codes. |
|
04/25/2007 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. Emergency vents for Class I, II and IIIA liquids shall not discharge inside buildings. The venting shall be installed and maintained in accordance with Section 2.2.5.2 of NFPA 30. · The tanks shall be equipped with emergency venting of the appropriate relief volume required for each tank. These volume requirements can be found in NFPA 30. |