Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2007 | VIOL - MEANS OF EGRESS | Approved | Exit signs repaired. Exir door repair, lighting out for replacement bid. Deck chairs removed. 5-25 |
|
| 04/27/2007 | VIOL - MEANS OF EGRESS | Violation | Exit signs out in emergency mode. -Storage room, N.E. corner.____ 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator.2003 IFC ****Repair/Replace exit sign. |
|
| 04/27/2007 | VIOL - MEANS OF EGRESS | Violation | Exit door hard to open. -South exit sleeping room.____ 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. Security devices affecting means of egress shall be subject to approval of the fire code official. 2003 IFC ***Repair door to open easily, with less than 15 pounds pushing pressure. |
|
| 04/27/2007 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting out of service. -Main entrance stairway.____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the area. 2003 IFC ****Repair emergency lighting. |
|
| 04/27/2007 | VIOL - MEANS OF EGRESS | Violation | Deck chairs blocking hallway to sun porch.____ 1027.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. ****Remove chairs from hallway. |