Case: T07FR00742

Parcel: 124040770


Addresses:

1541 E 2ND ST

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
05/25/2007 VIOL - BUILDING SVCS & SYSTEMS Approved Junction box cover installed.
One extension cord in closet.
Cube adapters removed.
04/27/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical junction box needs a cover. (Mechanical room).____

605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes. 2003 IFC
****Replace cover.
04/27/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords in use to power equipment.
-Housekeeping closet.____
-T.V. room.____
-Living room.____

605.5 Extension cords. Extension cords and flexible cords shall
not be a substitute for permanent wiring. Extension cords and
flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with portable
appliances. 2003 IFC
***Replace with approved power sources.
04/27/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Multiplug cube adapters in use.
-All throughout the house, bedrooms.____

605.4 Multiplug adapters. Multiplug adapters, such as cube
adapters, unfused plug strips or any other device not complying
with the ICC Electrical Code shall be prohibited. 2003 IFC
****Replace with approved power sources.