Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR00733

Parcel: 12709011E


Addresses:

101 N WILMOT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T07FR00733

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2007 INSP - FULL Approved all approved
04/17/2007 INSP - FULL Violation 1). Fire drill shall conducted. Date shall be determined by 5-2-07. IFC 404.2
2). Sprinkler inspection report shall be submitted. IFC 901.6
3). In suites 230 and 229, all ceiling tiles shall be in place at all times. Currently there are occupied rooms where are not in place. IFC 703.1
4). Currently flammable residue is being left on paper. This practice shall stop immediately. IFC 110.1, 2703.
NO more than 10 gallons
5). No more than 10 gallons of flammable liquid shall be left outside cabinet. IFC 3404.3.4.3
6). Currently in telephone rooms (multiple 1st floor thru 8th floor), there is a need for approved fire stopping . The Tucson Fire Department recommends contractors trained in approved methods and listed materials only to be used to abate this these violations. IFC 703.1.1
7). Suite 323 exit light shall be repaired. IFC 1027