Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T07FR00694
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/09/2007 | INSP - FULL | Correction Required | 32003IFC-315.3.1 Storage beneath overhead projections from building. Combustible materials stored or displayed outside of buildings that are protected by automatic sprinklers shall not be stored or displayed under nonspeinkler eaves,canopies or other projections or overhangs. | |
04/25/2007 | INSP - FULL | Violation | Due date inspection on 4/24/07 not complete, need more time. | |
04/10/2007 | INSP - FULL | Violation | 2003 IFC-901.6 Fire extinguishers shall be seviced annually and shall have a current service tag attached. 2003 IFC-605.5 Extension cords shall nor be a substitute for permanent wiring. 2003 IFC-1011.2 Exit lights shall be illuminated at all times. internally or externally. 2003 IFC-903.4 The storage area outside canopy is used for storage and is not sprinklered. This area shall be protected by an automatic sprinkler system. |