Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR00657
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
04/09/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | IFC 2003: 901.7 System out of service. Stand pipe 1 The Tucson Fire Department must be notified every 14 days of the progress of repairs to the stand pipe system. 791 3234 SYSTEM DESIGN 2.The southwest stand pipes will remain out service until they pass a system test. IFC 2003 912.2.2 Existing Buildings 1.Proper signage to all parts of the fire protection systems must be included with the repairs and upgrade to the stand pipe system. The signage must include FDC ID, zone of protection, and pressures required. 2.TFD stand pipe signage: See attached. |