Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 04/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Extinguishers not mounted by exits: TFC 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). ______Mount extinguishers [K class] in an approved manner. |
|
| 04/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Pull station clear and identifiable: 904.11.4 Special provisions for automatic sprinkler systems. Automatic sprinkler systems protecting commercial- type cooking equipment shall be supplied from a separate, readily accessible, indicating-type control valve that is identified. ______ Clear area around pull station and have clearly marked . |
|