Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00626
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/19/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
04/04/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | -Extension cords used as permanent wiring throughout sales floor, also extension cords plugged into each other in series.(Daisy chained)__ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 2003 IFC ***Replace extension cords with approved power supplies. |
|
04/04/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | -Panels blocked, combustible storage in Electrical room.__ 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. 2003 IFC ***Remove ALL combustible storage from electrical room. |