Case: T07FR00626

Parcel: 13355231A

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00626

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
04/19/2007 VIOL - BUILDING SVCS & SYSTEMS Approved
04/04/2007 VIOL - BUILDING SVCS & SYSTEMS Violation -Extension cords used as permanent wiring throughout sales floor, also extension cords plugged into each other in series.(Daisy chained)__
605.5 Extension cords. Extension cords and flexible cords shall
not be a substitute for permanent wiring. Extension cords and
flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with portable
appliances. 2003 IFC
***Replace extension cords with approved power supplies.
04/04/2007 VIOL - BUILDING SVCS & SYSTEMS Violation -Panels blocked, combustible storage in Electrical room.__
315.2.3 Equipment rooms. Combustible material shall not be
stored in boiler rooms, mechanical rooms or electrical equipment
rooms. 2003 IFC
***Remove ALL combustible storage from electrical room.