Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T07FR00617
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2007 | INSP - FULL | Approved | The sprinkler connections have been abated in a satisfactory manner. The insulation have been corrected as well as guards (cages) placed over the sprinkler heads to protect them. | |
04/18/2007 | INSP - FULL | Correction Required | I have been to this property several times. I spoke to the manager once again. I explained the issues with her and she is gong to have a 45 degree elbow put in to replace the 90 degree elbow. She is also abating the insulation problem under the rear awning. | |
04/05/2007 | INSP - FULL | Continued | The FDC's have been relocated. The sprinklers in the new construction still need to be relocated. They are in contact with the insulation. | |
04/03/2007 | INSP - FULL | Correction Required | Capt Holmes reported a Fire Dept problem with Sprinkler system inspector Davis assigned | |
04/03/2007 | INSP - FULL | Correction Required | jdavis2 assigned. |