Inspection History Details
Inspection Status: Compliance
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2007 | INSP - FULL | Compliance | Final on the reinspection. The three hour separation from B & F1 was complete. The two flammable liquid cabinets were installed. |
|
| 03/29/2007 | INSP - FULL | Scheduled | 2003 IFC-302.2.2 A 3-hour fire door shall be installed between the office and the factory, b to a F-1. 2003 IFC-3404.3.5.1 A flammable liquid cabinet shall in place in shop for the flammable and commbustable. 2003 IFC-605 The parts cleaner liquid is a combustable there for the electrical outlet shall be a GFI outlet. 2003 IFC-304.1 The yard storage: Vegetation growth shall be cut back or removed to prevent brush fires. 2003 IFC-3405.2.4 55- gallon drums shall have an approved pump taking suction through an opening in top of the container or tank. Class 1B, 1C, 11. & 111 liquids shall have a self closing or automatic closing valve. |