Case: T07FR00605

Parcel: 12419027A


Addresses:

728 S CAMPBELL AV

Inspection Status: Compliance

Inspection History: INSP - FULL

Date Description Inspector Results Comments
05/02/2007 INSP - FULL Compliance Final on the reinspection.
The three hour separation from B & F1 was complete.
The two flammable liquid cabinets were installed.
03/29/2007 INSP - FULL Scheduled 2003 IFC-302.2.2 A 3-hour fire door shall be installed between the office and the factory, b to a F-1.
2003 IFC-3404.3.5.1 A flammable liquid cabinet shall in place in shop for the flammable and commbustable.
2003 IFC-605 The parts cleaner liquid is a combustable there for the electrical outlet shall be a GFI outlet.
2003 IFC-304.1 The yard storage: Vegetation growth shall be cut back or removed to prevent brush fires.
2003 IFC-3405.2.4 55- gallon drums shall have an approved pump taking suction through an opening in top of the container or tank. Class 1B, 1C, 11. & 111 liquids shall have a self closing or automatic closing valve.