Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T07FR00601
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2007 | INSP - FULL | Approved | ||
03/29/2007 | INSP - FULL | Violation | 1). Fire drill is required. Please indicate the date for this drill by 4- 26-07. IFC 404.2 2). Elevator rags shall be removed, and all vents cleaned of oily residue. IFC 315.2.3 and in 1030 mech room. 3). Firestopping shall be completed, but not limited to the following areas: IFC 703.1.1 5th floor electrical, 4th floor electrical room, 2nd floor electrical, 4th floor telephone 4). Compass: remove decoration from sprinkler head. IFC 901.6 5). 3rd floor Blue Cross: Remove plant from ceiling tiles. IFC 703.1, IFC 901.6 6). In the following areas, obstructions are within 2 feet from the ceiling, possibly blocking sprinkler water flow. Suite 1075, suite 230, 5400, ADP 7). Create aisles in storage in space 13 and 8 in storage areas. IFC 1027 8). Repair gate preventing exit to basement in 5285. IFC 1027 |