Case: T07FR00598

Parcel: 12201024G


Addresses:

3942 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00598

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
04/17/2007 VIOL - MEANS OF EGRESS Approved Bolt locks have been removed. Security grilles are allowed if open while occupied, for security after hours only...
03/29/2007 VIOL - MEANS OF EGRESS Violation Bolt locks on back door:
TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.

______Remove all slide bolts and hardware. [note: The only lock may be a thumb turn bolt- 1 lock only]
03/29/2007 VIOL - MEANS OF EGRESS Violation Rear security grille:
Ok if unlocked while occupied. Security only!
03/29/2007 VIOL - MEANS OF EGRESS Violation Front security grille:
1008.1.3.5 Security grilles. In Groups B, F,Mand S, horizontal sliding or vertical security grilles are permitted at the main exit and shall be openable from the inside without the use of a key or
special knowledge or effort during periods that the space is occupied. The grilles shall remain secured in the full-open position during the period of occupancy by the general public.

______A readily visible durable sign is posted on the egress side on or adjacent to the door stating:
THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting [TFC 1008.1.8.3 Locks and latches]