Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00598
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/17/2007 | VIOL - MEANS OF EGRESS | Approved | Bolt locks have been removed. Security grilles are allowed if open while occupied, for security after hours only... | |
03/29/2007 | VIOL - MEANS OF EGRESS | Violation | Bolt locks on back door: TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ______Remove all slide bolts and hardware. [note: The only lock may be a thumb turn bolt- 1 lock only] |
|
03/29/2007 | VIOL - MEANS OF EGRESS | Violation | Rear security grille: Ok if unlocked while occupied. Security only! |
|
03/29/2007 | VIOL - MEANS OF EGRESS | Violation | Front security grille: 1008.1.3.5 Security grilles. In Groups B, F,Mand S, horizontal sliding or vertical security grilles are permitted at the main exit and shall be openable from the inside without the use of a key or special knowledge or effort during periods that the space is occupied. The grilles shall remain secured in the full-open position during the period of occupancy by the general public. ______A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting [TFC 1008.1.8.3 Locks and latches] |