Case: T07FR00587

Parcel: 12201024G


Addresses:

3940 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00587

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
04/27/2007 VIOL - BUILDING SVCS & SYSTEMS Approved Electrical violations abated.
03/28/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:
TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____Replace with approved power strip.
03/28/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Open space in electrical panel:
TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

_____Place an approved "blank" in the space.
03/28/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Blocked electrical panel:
TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.

______Clear area in front of electrical panel in an approved manner.