Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FLAMMABLE LIQUIDS
Case Number - T07FR00582
Inspection Description - VIOL - FLAMMABLE LIQUIDS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2007 | VIOL - FLAMMABLE LIQUIDS | Approved | ||
03/27/2007 | VIOL - FLAMMABLE LIQUIDS | Violation | IFC 3404.2.12.2- Testing of underground tanks. Before tank can be placed in operation, it shall be tested in accordance with state and local regulations. 1. Inventory control (Veeder Root) shall be tested annually by a third party to ensure accuracy. Results shall be submitted to TFD. 2. Cathodic protection shall be inspected annually. Report shall be submitted to TFD. 3. Coating on interior of steel tank was identified as damaged and inadequate. |