Inspection History Details
Inspection Status: Approved
Inspection History: INSP - SPECIAL EVENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2007 | INSP - SPECIAL EVENT | Approved | Tentative TFD approvalgranted, provided compliance with TFD's "Festival and Civic Event Guidelines" (provided). Special Event Site Visit 3/28 3:30pm w/Ralph. Plans NO tents/canopies Plans NO cooking/open flames Expected Occ Load = 760-780 people Courtyard area 23,000 SqFt A2 unconcentrated seating (15'/person factor) Max Occ Load for area = 1,500. Exit width is sufficient for area Unsprinklered (.2"/person factor) 396" exit width (4 locations, appropriate distance and locaiton) could serve 1,980. |