Case: T07FR00546

Parcel: 14016011A


Addresses:

1830 E IRVINGTON RD


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00546

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
05/04/2007 VIOL - BUILDING SVCS & SYSTEMS Approved All o.k. 5/4
04/12/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords used to power equipment.___
-Managers' office___
-In front of meat cooler___
-Within all checkout registers___
-(2) in training room___
-Rear stockroom charger area (cord routed above closet)___

605.5 Extension cords. Extension cords and flexible cords shall
not be a substitute for permanent wiring. Extension cords and
flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with portable
appliances. 2003 IFC
****Remove ALL extension cords, use approved power sources.
04/12/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Junction box above receiving door is missing cover.___

605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes. 2003 IFC
****Replace junction box cover.