Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00546
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/04/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | All o.k. 5/4 | |
04/12/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Extension cords used to power equipment.___ -Managers' office___ -In front of meat cooler___ -Within all checkout registers___ -(2) in training room___ -Rear stockroom charger area (cord routed above closet)___ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 2003 IFC ****Remove ALL extension cords, use approved power sources. |
|
04/12/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Junction box above receiving door is missing cover.___ 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 2003 IFC ****Replace junction box cover. |