Inspection History Details
Inspection Status: Compliance
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00543
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2007 | VIOL - MEANS OF EGRESS | Compliance | ALL O.K. 4/5 | |
03/22/2007 | VIOL - MEANS OF EGRESS | Violation | -Exit signs out of service. (S.E. entrance) (East emergency exit) (Receiving exit door) 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. 2003 IFC ___ Repair signs to working order. |
|
03/22/2007 | VIOL - MEANS OF EGRESS | Violation | -Emergency lighting out of service. (All units in store) 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the area. 2003 IFC ___ Repair ALL emergency lighting units. |