Case: T07FR00543

Parcel: 119215910


Addresses:

1740 W AJO WY


Inspection Status: Compliance

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR00543

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Compliance

Date Description Inspector Results Comments
05/02/2007 VIOL - FIRE PROTECTION SYSTEMS Compliance ALL O.K. 4/5
03/22/2007 VIOL - FIRE PROTECTION SYSTEMS Violation -Fire Department Connection (FDC) caps missing.
912.6 Inspection, testing and maintenance. All fire department
connections shall be periodically inspected, tested and maintained in accordance with NFPA 25. 2003 IFC
___ Install caps on FDC's.
03/22/2007 VIOL - FIRE PROTECTION SYSTEMS Violation -Fire extinguishers overdue for inspection. (N.E. corner) (Mechanical room)
-Send Fire alarm test results to Fire Dept
-Corroded sprinkler head in Meat dept.
-Two more sprinkler heads needed in sprinkler head box. (Riser)
901.6 Inspection, testing and maintenance. Fire detection,
Alarm and extinguishing systems shall be maintained in an operative
condition at all times, and shall be replaced or repaired
where defective. Nonrequired fire protection systems and equipment
shall be inspected, tested and maintained or removed. 2003 IFC
___ Extinguishers shall be tested immediately.
___ Test alarm system, send results to F.D.
___ Replace corroded head.
___ Provide at least two more sprinkler heads in box.
03/22/2007 VIOL - FIRE PROTECTION SYSTEMS Violation -Extend sprinkler head coverage. (Area by dairy back room.)
901.4 Installation. Fire protection systems shall be maintained
in accordance with the original installation standards for that
system. Required systems shall be extended, altered, or augmented
as necessary to maintain and continue protection whenever
the building is altered, remodeled or added to. Alterations
to fire protection systems shall be done in accordance with applicable standards. 2003 IFC
___ Install sprinkler heads to provide said coverage.