Inspection History Details
Inspection Status: Compliance
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00543
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | Compliance | ALL O.K. 4/5 | |
03/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | -Extension cords used to power permanent equipment. (ATM in checkout area) (check cashing office [2] ) 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 2003 IFC ___ Remove extension cords, use approved power sources. |
|
03/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | -Switch blanks missing in electrical panels. -Outlet covers missing or damaged. (Liquor dept.) (Produce backdoor) (Cashier #2) (Junction box in upstairs office area) 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 2003 IFC ___ Replace/repair covers. |