Case: T07FR00543

Parcel: 119215910


Addresses:

1740 W AJO WY


Inspection Status: Compliance

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00543

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Compliance

Date Description Inspector Results Comments
05/02/2007 VIOL - BUILDING SVCS & SYSTEMS Compliance ALL O.K. 4/5
03/22/2007 VIOL - BUILDING SVCS & SYSTEMS Violation -Extension cords used to power permanent equipment.
(ATM in checkout area)
(check cashing office [2] )
605.5 Extension cords. Extension cords and flexible cords shall
not be a substitute for permanent wiring. Extension cords and
flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with portable
appliances. 2003 IFC
___ Remove extension cords, use approved power sources.
03/22/2007 VIOL - BUILDING SVCS & SYSTEMS Violation -Switch blanks missing in electrical panels.
-Outlet covers missing or damaged.
(Liquor dept.)
(Produce backdoor)
(Cashier #2)
(Junction box in upstairs office area)
605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes. 2003 IFC
___ Replace/repair covers.