Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00538
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/27/2007 | VIOL - MEANS OF EGRESS | Approved | all abated. | |
03/21/2007 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: TFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: ______Fix all inoperative emergency lights. |
|
03/21/2007 | VIOL - MEANS OF EGRESS | Violation | Roll down security on front door:: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _______Disengage rolldown security on front door [only] or place bolts through frame to ensure that is stays open at all times. |