Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00534
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/03/2007 | VIOL - MEANS OF EGRESS | Approved | All o.k. 5/3 | |
05/02/2007 | VIOL - MEANS OF EGRESS | Compliance | o.k. except for exit not opening freely. Reinspection forthcoming. 4/4 | |
03/20/2007 | VIOL - MEANS OF EGRESS | Violation | -Exit door does not open freely, needs adjustment. (West produce) 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. A maximum unlatching force of 15 pounds (67 N). **Repair door. |
|
03/20/2007 | VIOL - MEANS OF EGRESS | Violation | -Exit signs out of service in emergency mode. (Throughout store) 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. 2003 IFC ***Repair ALL exit signs to working order. |
|
03/20/2007 | VIOL - MEANS OF EGRESS | Violation | -Emergency lighting out of service. (Throughout store) 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the area. 2003 IFC ***Repair lighting to working order. |