Case: T07FR00534

Parcel: 11941176H


Addresses:

1775 W AJO WY


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00534

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
05/03/2007 VIOL - MEANS OF EGRESS Approved All o.k. 5/3
05/02/2007 VIOL - MEANS OF EGRESS Compliance o.k. except for exit not opening freely. Reinspection forthcoming. 4/4
03/20/2007 VIOL - MEANS OF EGRESS Violation -Exit door does not open freely, needs adjustment. (West produce)
1008.1.9 Panic and fire exit hardware. Where panic and fire
exit hardware is installed, it shall comply with the following:
1. The actuating portion of the releasing device shall extend
at least one-half of the door leaf width.
2. A maximum unlatching force of 15 pounds (67 N).
**Repair door.
03/20/2007 VIOL - MEANS OF EGRESS Violation -Exit signs out of service in emergency mode. (Throughout store)
1026.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated from
an external source, shall have an intensity of not less than 5
foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose. 2003 IFC
***Repair ALL exit signs to working order.
03/20/2007 VIOL - MEANS OF EGRESS Violation -Emergency lighting out of service. (Throughout store)
1006.3 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the area. 2003 IFC
***Repair lighting to working order.