Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR00534

Parcel: 11941176H


Addresses:

1775 W AJO WY


Inspection Status: Compliance

Inspection History: VIOL - FIRE RESIST.RATED CONST

Case Number - T07FR00534

Inspection Description - VIOL - FIRE RESIST.RATED CONST

Inspection Status - Compliance

Date Description Inspector Results Comments
05/02/2007 VIOL - FIRE RESIST.RATED CONST Compliance o.k. 4/4
03/20/2007 VIOL - FIRE RESIST.RATED CONST Violation -Ceiling panels missing.
-Walkway to rear closet
-Stockroom (various locations)
703.1 Maintenance. The required fire-resistance rating of
fire-resistance-rated construction (including walls, fire stops,
shaft enclosures, partitions and floors) shall be maintained.
Such elements shall be properly repaired, restored or replaced
when damaged, altered, breached or penetrated. Openings
made therein for the passage of pipes, electrical conduit, wires,
ducts, air transfer openings, and holes made for any reason shall
be protected with approved methods capable of resisting the
passage of smoke and fire. 2003 IFC
***Replace missing panels.