Inspection Status: Compliance
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00534
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | Compliance | all o.k. 4/4 | |
03/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | -Extension cords in use in place of permanent wiring. -Mechanical room -Northeast entrance (2) 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 2003 IFC ***Replace with approved power source. |
|
03/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | -Multiplug adapter in use. (Stockroom office) 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. 2003 IFC ***Replace with UL approved power strip. |
|
03/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | -Missing switch/outlet cover plates. -Entrance to produce room -Meat dept. -Stock room office -Exposed wiring -Entrance to stock room -Missing switch covers in electrical panel -Stockroom 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 2003 IFC ***Repair/replace, install covers. |
|
03/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | -Blocked electrical panels. (Stockroom) 605.3 Working spaces. The working space shall not be less than the width of the electrical service equipment. No storage of any materials shall be located within the designated working space. 2003 IFC ***Keep panel spaces clear. |