Case: T07FR00534

Parcel: 11941176H


Addresses:

1775 W AJO WY

Inspection Status: Compliance

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
05/02/2007 VIOL - PRECAUTION AGAINST FIRE Compliance All o.k. 4/4
03/20/2007 VIOL - PRECAUTION AGAINST FIRE Violation -Mechanical room storage, housekeeping.
315.2.3 Equipment rooms. Combustible material shall not be
stored in boiler rooms, mechanical rooms or electrical equipment
rooms. 2003 IFC
***Remove ALL combustible storage from mechanical room.
03/20/2007 VIOL - PRECAUTION AGAINST FIRE Violation -Sprinkler head blocked. (wall deli)
315.2.1 Ceiling clearance. Storage shall be maintained 2 feet
(610 mm) or more below the ceiling in nonsprinklered areas of
buildings or a minimum of 18 inches (457 mm) below sprinkler
head deflectors in sprinklered areas of buildings. 2003 IFC
***Keep storage within limits. (This was fixed in my presence.)