Case: T07FR00512

Parcel: 13409019L

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
04/06/2007 INSP - FULL Correction Required The spray booth is not sprinkled, but the owner is going to a water base paint. I'll check back in a week. The owner is also moving.
03/16/2007 INSP - FULL Violation 2003 IFC-1503.2.2 Open flames and sparks-ducing devices shall not be located in spray spaces or vapor area located within 20 feet.
2003 IFC-1504.6 Fire protection. Spray booths shall be protected by an approved automatic fire-extinguishing system, which shall also protect exhaust plenums, exhaust ducts, and both sides of dry filters.
I will check with Captain Summers on the water base products and I will call you on this.
2003 IFC-105.3.3 The Certificate of Occupancy shall be posted or in the files at the business.