Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00505
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/03/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | All violations abated. 5/3 | |
03/16/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 1. Extension cord used to power equipment. 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 2003 IFC ***Replace extension cord with UL approved power supply. |
|
03/16/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2. Open junction boxes behind corner sign. 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 2003 IFC ***Keep all junction boxes closed, secured. |