Case: T07FR00504

Parcel: 12904287A


Addresses:

345 S KINO PW


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T07FR00504

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
03/28/2007 INSP - FULL Approved All violations complete, no further action at this tiome.
03/15/2007 INSP - FULL Violation 2003 IFC-901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replace or repaired where defective. Sprinkler system shall be serviced annually and shall have a current service tag attached.
2003 IFC-605.3.1 Labeling. Doors into electrical, or mechanical rooms shall be marked with plainly visible and legible sign ststing MECHANICAL ROOM.
2003 IFC-605.5 Extension cords shall not be a substitute for permanent wiring: This is in the Kooler Box room.
2003 IFC-906 Riser Room: shall be identifed riser room. The two doors leading to the riser room shall be labeled riser room so firefighters can locate quicker.
2003 IFC-904.10.1 System test, system shall be inspected and tested for proper operation at 12 months intervals.