Case: T07FR00503

Parcel: 132171390

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
06/26/2007 VIOL - MEANS OF EGRESS Approved All corrections have been completed.
03/19/2007 VIOL - MEANS OF EGRESS Violation 1008.1.8.3 Locks and latches. Locks and latches shall be permitted
to prevent operation of doors where a readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.
Replace double key locking cylinder with a thumb bolt latch or place a sign overhead and keep door unlocked. 1)North exit door to lunch room 2) Door nearest to Harly proofer on North wall
03/19/2007 VIOL - MEANS OF EGRESS Violation 1011.2 Illumination. All required exits shall be marked with an internally or externally illuminated exit sign. Cause your exit signs to be illuminated.
03/19/2007 VIOL - MEANS OF EGRESS Violation 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. 1) Emergency lighting in front office is not operating...replace battery or bulbs to cause it to perate.
03/19/2007 VIOL - MEANS OF EGRESS Violation 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. Remove bolts from 1) SW corner of building 2) South East exit door nearest print press