Case: T07FR00503

Parcel: 132171390

Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
06/13/2007 VIOL - PRECAUTION AGAINST FIRE Approved corrected
03/20/2007 VIOL - PRECAUTION AGAINST FIRE Violation 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. Maintain 18 inches clearance from sprinklers in lobby closet.
03/20/2007 VIOL - PRECAUTION AGAINST FIRE Violation 304.1.1 Waste material. Accumulations of wastepaper, wood, hay, straw, weeds, litter or combustible or flammable waste or rubbish of any type shall not be permitted to remain on a roof or in any court, yard, vacant lot, alley, parking lot, open space, or beneath a grandstand, bleacher, pier, wharf, manufactured home, recreational vehicle or other similar structure. Remove baled boxes, excess vegitation, and wood palets in South lots.