Case: T07FR00503

Parcel: 132171390

Inspection Status: Approved

Inspection History: INSP - LIFE SAFETY

Date Description Inspector Results Comments
06/13/2007 INSP - LIFE SAFETY Approved corrected
03/19/2007 INSP - LIFE SAFETY Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Remove all extension cords being used as permanent wiring. 1) on North side attached to Harly Proofer and work bench electric strip. 2) in reception/ Steves office. 3) connected to extruder 4) On breached wall along ceiling to South East ( near extruder ).
03/19/2007 INSP - LIFE SAFETY Violation 605.6 Unapproved conditions. Approved covers shall be provided for all switch and electrical outlet boxes. 1)Replace missing faceplate for outlet in Steve's office. 2) Place blanks or covers in electric panel behind print press.
03/19/2007 INSP - LIFE SAFETY Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. 1) repair conduit on wall behind bailer. 2) replace cover to electrical wiring on print press.
03/19/2007 INSP - LIFE SAFETY Violation 605.3 Working space and clearance. No storage of any materials shall be located within the designated working space. 1) Move bailer so as not to block electrical panel.