Case: T07FR00495

Parcel: 13612833C

Inspection Status: Approved

Inspection History: INSP - LIFE SAFETY

Case Number - T07FR00495

Inspection Description - INSP - LIFE SAFETY

Inspection Status - Approved

Date Description Inspector Results Comments
03/19/2007 INSP - LIFE SAFETY Approved All extnguishers in clear visability and accessable. The test results for the sprinkler system will be provided during the full inspection which is done on 03-19-2007 (T07FR00496). Electrical panels clear of combustables.
03/15/2007 INSP - LIFE SAFETY Correction Required 906.6 Unobstructed and unobscured. Fire extinguishers
shall not be obstructed or obscured from view.
-Maintain clearnece around fire extinguishers.
03/15/2007 INSP - LIFE SAFETY Correction Required 901.6.1 Standards. Fire protection systems shall be inspected,
tested and maintained in accordance with the referenced
standards listed in Table 901.6.1.
- Provide annual testing of extinguishers and sprinklers
03/15/2007 INSP - LIFE SAFETY Correction Required 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment.
- clear area in front of electrical panel.