Inspection History Details
Inspection Status: Approved
Inspection History: INSP - LIFE SAFETY
Case Number - T07FR00495
Inspection Description - INSP - LIFE SAFETY
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/19/2007 | INSP - LIFE SAFETY | Approved | All extnguishers in clear visability and accessable. The test results for the sprinkler system will be provided during the full inspection which is done on 03-19-2007 (T07FR00496). Electrical panels clear of combustables. | |
03/15/2007 | INSP - LIFE SAFETY | Correction Required | 906.6 Unobstructed and unobscured. Fire extinguishers shall not be obstructed or obscured from view. -Maintain clearnece around fire extinguishers. |
|
03/15/2007 | INSP - LIFE SAFETY | Correction Required | 901.6.1 Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed in Table 901.6.1. - Provide annual testing of extinguishers and sprinklers |
|
03/15/2007 | INSP - LIFE SAFETY | Correction Required | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. - clear area in front of electrical panel. |