Case: T07FR00494

Parcel: 13002003A


Addresses:

3030 E 22ND ST


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00494

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
04/05/2007 VIOL - MEANS OF EGRESS Approved Abated 4/3
03/15/2007 VIOL - MEANS OF EGRESS Violation -Exit signs out of service.
-North entrance
-South entrance
-South stockroom exit
1026.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated from
an external source, shall have an intensity of not less than 5
foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose. 2003 IFC
***Repair signs. Stockroom needs entire sign replaced.
03/15/2007 VIOL - MEANS OF EGRESS Violation -Emergency lighting out of service.
-North entrance
-South entrance
-South stockroom entrance
1006.3 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premise's electrical supply.
In the event of power supply failure, an emergency electrical
system shall automatically illuminate area. 2003 IFC
***Repair lighting.
03/15/2007 VIOL - MEANS OF EGRESS Violation -Egress path blocked. (South stockroom exit)
1027.2 Reliability. Required exit accesses, exits or exit discharges
shall be continuously maintained free from obstructions
or impediments to full instant use in the case of fire or other
emergency. 2003 IFC
***Keep exit pathway clear at all times.
03/15/2007 VIOL - MEANS OF EGRESS Violation -Exit door difficult to open, needs adjustment. (South stockroom Exit)
1008.1.9 Panic and fire exit hardware. Where panic and fire
exit hardware is installed, it shall comply with the following:
1. The actuating portion of the releasing device shall extend
at least one-half of the door leaf width.
2. A maximum unlatching force of 15 pounds (67 N).
***Repair door.