Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00494
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/05/2007 | VIOL - MEANS OF EGRESS | Approved | Abated 4/3 | |
03/15/2007 | VIOL - MEANS OF EGRESS | Violation | -Exit signs out of service. -North entrance -South entrance -South stockroom exit 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. 2003 IFC ***Repair signs. Stockroom needs entire sign replaced. |
|
03/15/2007 | VIOL - MEANS OF EGRESS | Violation | -Emergency lighting out of service. -North entrance -South entrance -South stockroom entrance 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate area. 2003 IFC ***Repair lighting. |
|
03/15/2007 | VIOL - MEANS OF EGRESS | Violation | -Egress path blocked. (South stockroom exit) 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. 2003 IFC ***Keep exit pathway clear at all times. |
|
03/15/2007 | VIOL - MEANS OF EGRESS | Violation | -Exit door difficult to open, needs adjustment. (South stockroom Exit) 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. A maximum unlatching force of 15 pounds (67 N). ***Repair door. |