Case: T07FR00494

Parcel: 13002003A


Addresses:

3030 E 22ND ST


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00494

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
04/05/2007 VIOL - BUILDING SVCS & SYSTEMS Approved Abated 4/3
03/15/2007 VIOL - BUILDING SVCS & SYSTEMS Violation -Extension cords used to power equipment.
-Outside grocery freezer
-lighting in breakroom
-Fan in breakroom bathroom
-Storage room by Meat dept.
-In Meat dept.
-Behind customer service desk
605.5 Extension cords. Extension cords and flexible cords shall
not be a substitute for permanent wiring. Extension cords and
flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with portable
appliances. 2003 IFC
***Replace extension cords with approved power supplies.
03/15/2007 VIOL - BUILDING SVCS & SYSTEMS Violation -Open electrical junction box. (shipping/receiving)
-Damaged outlet box. (outside, north soda machines)
605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes. 2003 IFC
***Repair boxes.