Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00494
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/05/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | Abated 4/3 | |
03/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | -Extension cords used to power equipment. -Outside grocery freezer -lighting in breakroom -Fan in breakroom bathroom -Storage room by Meat dept. -In Meat dept. -Behind customer service desk 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 2003 IFC ***Replace extension cords with approved power supplies. |
|
03/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | -Open electrical junction box. (shipping/receiving) -Damaged outlet box. (outside, north soda machines) 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 2003 IFC ***Repair boxes. |