Inspection Status: Approved
Inspection History: VIOL - FIRE SERVICE FEATURES
Case Number - T07FR00494
Inspection Description - VIOL - FIRE SERVICE FEATURES
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2007 | VIOL - FIRE SERVICE FEATURES | Approved | Sign installed 5/17 | |
04/05/2007 | VIOL - FIRE SERVICE FEATURES | Violation | Sign was spray painted on door, needs to be an actual permanent sign. 4/3 | |
03/15/2007 | VIOL - FIRE SERVICE FEATURES | Violation | -Large center door blocked from inside. (south wall) 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. Required fire department access doors shall not be obstructed or eliminated. Exit and exit access doors shall comply with Chapter 10. Access doors for high-piled combustible storage shall comply with Section 2306.6.1. 2003 IFC ***Install sign on door. |