Case: T07FR00479

Parcel: 13809007G


Addresses:

428 W VALENCIA RD


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR00479

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
05/02/2007 VIOL - FIRE PROTECTION SYSTEMS Approved All o.k., with exception of 1 sprinkler head still needs replacing in meat freezer.
03/14/2007 VIOL - FIRE PROTECTION SYSTEMS Violation -Fire extinguishers blocked, needs signage. (Bakery, Receiving)
906.6 Unobstructed and unobscured. Fire extinguishers shall
not be obstructed or obscured from view. In rooms or areas in
which visual obstruction cannot be completely avoided, means
shall be provided to indicate the locations of extinguishers. 2003 IFC
**Clear obstructions, install signs above extinguishers.
03/14/2007 VIOL - FIRE PROTECTION SYSTEMS Violation -Fire extinguishers need to be mounted. (Produce office, motor room)
906.7 Hangers and brackets. Hand-held portable fire
extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be se-
curely anchored to the mounting surface in accordance with the
manufacturer's installation instructions. 2003 IFC
**Mount extinguishers in approved manner.
03/14/2007 VIOL - FIRE PROTECTION SYSTEMS Violation -Sprinkler heads (3) need replacing due to corrosion. (Meat walk-in cooler)
-Sprinkler head painted over. (Entrance to rear bathrooms.)
901.6 Inspection, testing and maintenance. Fire detection,
Alarm and extinguishing systems shall be maintained in an operative
condition at all times, and shall be replaced or repaired
where defective. Nonrequired fire protection systems and equipment
shall be inspected, tested and maintained or removed. 2003 IFC
**Replace corroded/painted sprinkler heads.
03/14/2007 VIOL - FIRE PROTECTION SYSTEMS Violation -Sprinkler head needed in countdown room.
901.4 Installation. Fire protection systems shall be maintained
in accordance with the original installation standards for that
system. Required systems shall be extended, altered, or augmented
as necessary to maintain and continue protection whenever
the building is altered, remodeled or added to. Alterations
to fire protection systems shall be done in accordance with applicable standards. 2003 IFC
**Install sprinkler head to protect countdown room.