Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR00479
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | All o.k., with exception of 1 sprinkler head still needs replacing in meat freezer. | |
03/14/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | -Fire extinguishers blocked, needs signage. (Bakery, Receiving) 906.6 Unobstructed and unobscured. Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. 2003 IFC **Clear obstructions, install signs above extinguishers. |
|
03/14/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | -Fire extinguishers need to be mounted. (Produce office, motor room) 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be se- curely anchored to the mounting surface in accordance with the manufacturer's installation instructions. 2003 IFC **Mount extinguishers in approved manner. |
|
03/14/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | -Sprinkler heads (3) need replacing due to corrosion. (Meat walk-in cooler) -Sprinkler head painted over. (Entrance to rear bathrooms.) 901.6 Inspection, testing and maintenance. Fire detection, Alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 2003 IFC **Replace corroded/painted sprinkler heads. |
|
03/14/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | -Sprinkler head needed in countdown room. 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. 2003 IFC **Install sprinkler head to protect countdown room. |